fbpx

HOTLINE

AU: 1300 387 587

NZ: 0800 106 266

SEAT EXTRACTION FANS
CENTRIFUGAL FANS FOR
CORROSIVE APPLICATIONS

SEAT Extraction Fans

Constructed with thick polypropylene housing for maximum protection against acids, the SEAT Series is ready to take on and exhaust fumes from highly corrosive environments.

Features

Cowl rotates to eight discharge positions by 45° increments.

Stainless steel hardware.

Forward curved centrifugal impeller.

Direct drive, asynchronous motor, single or three phase, IP55.

Five models with air flows from 50 to 9000 m³/h.

10 to 1400Pa total pressure.

Available in ATEX version.

ModelAir Flow Range
SEAT 1550-700 m³/h
SEAT 20200-700 m³/h
SEAT 25500-3000 m³/h
SEAT 30700-4500 m³/h
SEAT 351800-9000 m³/h

Dimensions

Product CodeABCØDEFGHJK**LMN
SEAT15...17024020312510032307080360180340311
SEAT20...20830324016010057328494390180340311
SEAT25...248365310200103923595105515180420390
SEAT30...30045037325011711235110120540240460460
SEAT35*...37057045031513017060150170792350600580

* LG Position available only.
** Longest frame size shown.
Dimensions in mm

Handings are viewed from inlet side – 45 degree adjustable

Technical Data

Product
Code
Fan Speed rev/secAvg. dB(A) @ 3m*1ph3phMax. Amb °C**App. Wt. kgHanding
kWAmpskWAmps
SEAT15248540.372.700.371.04608.1LG or RD
SEAT15424420.252.200.250.90608.3LG or RD
SEAT1561630--0.180.68608.3LG or RD
SEAT20248640.754.731.102.406015.9LG or RD
SEAT20424490.252.200.250.90609.0LG or RD
SEAT2061640--0.180.68609.7LG or RD
SEAT2524867--3.005.786036.0LG or RD
SEAT25424530.372.900.371.106011.9LG or RD
SEAT2561643--0.180.686011.4LG or RD
SEAT30424591.107.001.102.686023.7LG or RD
SEAT3061649--0.752.226019.6LG or RD
SEAT3542467--5.5011.006053.0LG
SEAT3561658--2.205.386043.2LG

* Inlet Sound Levels
**Max temperature of air in duct