TD EVO VAR
DUAL CONTROL IN-LINE DUCT MOUNTED FAN
TD EVO VAR
The TD EVO VAR in-line fan has been designed to provide highly efficient performance with low energy consumption for domestic and commercial applications. It can be speed controlled via an on-board potentiometer, or remotely via a 0-10V or 4-20mA analogue input signal.
The TD EVO VAR also comes standard with an on-board, adjustable 1 to 30 minute run-on-timer that allows steam and odour to be exhausted after leaving the room.
TD EVO VAR is suitable for toilets, bathrooms, ensuites, laundries and kitchens in homes, hotels, apartments and commercial buildings. There are 6 models in the range matching standard duct sizes from 100 to 315mm diameter.
Features
High performance mixed-flow impeller.
Optimised impeller, guide vanes, and outlet diffuser for low noise operation.
Main fan body is easily removed without dismantling ducting.
Fan can be mounted in any position.
Dimensions
| Model No. | A | B | C | DØ | E | F | G | H | Weight kg |
|---|---|---|---|---|---|---|---|---|---|
| TD-EVO-100VAR | 302 | 181 | 201 | 97 | 29 | 107 | 133 | 100 | 1.7 |
| TD-EVO-125VAR | 302 | 191 | 221 | 123 | 29 | 117 | 132 | 100 | 1.8 |
| TD-EVO-150VAR | 326 | 221 | 240 | 147 | 25 | 126 | 165 | 120 | 3.0 |
| TD-EVO-200VAR | 346 | 238 | 263 | 197 | 28 | 137 | 190 | 124 | 4.1 |
| TD-EVO-250VAR | 390 | 289 | 306 | 247 | 40 | 159 | 230 | 155 | 6.2 |
| TD-EVO-315VAR | 485 | 353 | 371 | 312 | 40 | 159 | 278 | 188 | 8.4 |
Dimensions in mm
Technical Data
| Model No. | M³/h† | L/s† | Fan Speed Rev/Sec | AVG. dB(A) @ 3m* | 1PH | MAX. AMB °C | Volts | |
|---|---|---|---|---|---|---|---|---|
| Watts | AMPS | |||||||
| TD-EVO-100VAR | 210 | 58 | 41 | 31 | 16 | 0.1 | 60 | 220-240 |
| TD-EVO-125VAR | 310 | 86 | 39 | 36 | 29 | 0.1 | 60 | 220-240 |
| TD-EVO-150VAR | 560 | 156 | 44 | 44 | 45 | 0.2 | 60 | 220-240 |
| TD-EVO-200VAR | 900 | 250 | 45 | 47 | 107 | 0.5 | 60 | 220-240 |
| TD-EVO-250VAR | 1400 | 389 | 45 | 52 | 181 | 0.8 | 60 | 220-240 |
| TD-EVO-315VAR | 1840 | 511 | 44 | 56 | 273 | 1.1 | 60 | 220-240 |
* Inlet sound levels
† Air flow without duct and fittings